FP/FR1100/1200/2000 V6: Installation and Commissioning Manual 13
Power Supply
Characteristics
FP/FR1xxx &
FR2000
FP1216EN &
FP1264
FP/FR2xxx
FR2032/20128
FR2064/20255
- Battery flat
- Flat battery cut-out
- Earth fault
- Auxiliary supply
fault
- Battery flat
- Flat battery cut-out
- Earth fault
- Auxiliary supply
fault
- Battery flat
- Flat battery cut-out
Fuses AC fuse 0.8 A,
250 V, T
(20 mm STD fuse)
AC fuse – 2 A,
250 V, T
(20mm STD fuse)
AC fuse – 2 A
(20 mm STD fuse)
Aux. Output – 5 A
(20 mm STD fuse)
Battery fuse – 5 A
(20 mm STD fuse)
Fuse – 1 A
(20 mm STD fuse)
Maximum current
drawn from the
primary input
250 mA 1 A 1 A 0.3 A (no options
installed)
Maximum output
ripple voltage
± 300 mV ± 300 mV ± 300 mV
Fault Relay
(Configuration
depended on jumper
setting – refer to
section 6.4.2.2.)
Maximum switching
current:
2A @ 24 VDC
Maximum power
rating:
50 W
Maximum switching
current:
2 A @ 24VDC
Maximum power
rating:
50 W
- -