Fault
code
Fault type Possible cause Solution
SPI
Phase loss on the input
side
Phase loss or violent fluctuation
occurred on input R, S, T.
Check the input power.
Check the installation wiring.
SPO
Phase loss on output
side
Phase loss output occurs to U, V,
W (or the three phases of the
load are seriously asymmetrical)
Check the output wiring.
Check the motor and cable.
OH1
Rectifier module
overheating
Air duct jam or fan damage
occurs.
Ambient temperature is too high.
The time of overload running is
too long.
Dredge the vent duct or replace the
fan.
Lower the ambient
temperature.
OH2 VFD module overheat
EF External fault
SI external fault input terminals
action.
Check the external device input.
CE
RS485
communication fault
The baud rate setting is incorrect.
A fault occurs to the
communication wiring.
The communication address
is incorrect.
Communication suffers from
strong interference.
Set a proper baud rate.
Check the communication interface
wiring.
Set a proper communication
address.
Replace or change the wiring to
enhance the anti-interference
capability.
ItE Current detection fault
The control board connector is in
poor contact.
Hall device is damaged.
An exception occurs on the
magnifying circuit.
Check the connector and re-plug.
Replace the Hall device.
Change the main control board.
tE Motor autotuning fault
The motor capacity does not
match the VFD capacity.
Motor parameters are not set
correctly.
The difference between the
parameters obtained from
autotuning and the standard
parameters is great.
Autotuning timed out.
Change the VFD mode.
Set the motor type and
nameplate parameters correctly.
Empty the motor load.
Check the motor wiring and
parameter settings.
Check whether the upper limit
frequency is higher than 2/3 of the
rated frequency.
EEP
EEPROM operation
fault
Error in reading or writing control
parameters.
EEPROM is damaged.
Press STOP/RST for reset.
Change the main control board.
PIDE
PID feedback
disconnection
PID feedback is disconnected.
The PID feedback source
disappears.
Check the PID feedback signal
wires.
Check the PID feedback source.
END
Running time
reached
The actual running time of the
VFD is longer than the internal
set running Time
Ask the supplier to adjust the
preset running time.
OL3 Electronic overload
The VFD reports overload pre-
alarm
according to the setting.
Check the load and overload
pre-alarm threshold.
ETH1
To-ground
short-circuit fault 1
VFD output is short connected to
the ground.
There is a fault in the current
detection circuit.
Check whether the motor wiring is
proper.
Replace the Hall device.
Change the main control board.
ETH2
To-ground short-
circuit fault 2
tSF Hydraulic probe damage Hydraulic probe damage. Replace the hydraulic probe.