Fault
code
Fault type Possible cause Solution
dEu Speed deviation fault
The load is too heavy or stalled. Check the load and increase the
detection time if the load is normal.
Check whether control parameters
are set correctly.
STo Mal-adjustment fault
SM control parameters are set
incorrectly.
Autotuned parameters are not
accurate.
The VFD is not connected to
the motor.
Check the load and ensure the load
is normal.
Check whether control parameters
are set correctly.
Increase the maladjustment
detection time.
LL
Electronic
underload
The VFD reports underload
pre-alarm according to the
setting.
Check the load and underload
pre-alarm threshold.
PINV
PV reverse connection
fault
PV wiring is incorrect. Change the wiring direction of
positive and negative terminals, and
perform the wiring again.
PVOC PV overcurrent
ACC or DEC is too fast.
The power of the VFD is too low.
The load transients or is
abnormal.
There is to-ground short circuit
Increase the ACC/DCC time.
Select the VFD with larger power.
Check if the load is short circuited
(to-ground short circuit of line-to-line
short circuit) or the rotation is not
smooth
PVOV PV overvoltage
The solar cell panel input voltage
is too high.
Model -4 is set as another
model.
Reduce the number of solar cell
panels in series connection.
Check and reset the model.
PVLV PV undervoltage
The power of the solar cell panels
in series connection is too low or
it is cloudy and rainy weather.
The starting current of the motor
is too high.
Increase the number of solar cell
panels or perform the test in the
normal sunlight.
Replace the motor.
E-422
Fault on 422
communication with the
boost module
Communication cables are in
poor contact.
Check four communication cables of
422 communication, ensuring that
they are connected reliably.
OV
Bus overvoltage
detected on the boost
side
The sunlight changes sharply. Adjust the boost PI parameters,
and enlarge the values of P19.07
and P19.08.
A-LS Weak-light pre-alarm
The sunlight is weak or the
solar panel configuration
is insufficient.
The device will automatically run
when the light is sufficient.
Check whether the solar panel
configuration is sufficient.
A-LL Underload pre-alarm The pumping pool has no water. Check the pumping pool.
A-tF Full-water pre-alarm
The pumping pool is full. If you have configured the full-water
pre-alarm function, the device
automatically stops when the pre-
alarm elapsed. Otherwise, check
whether terminals are wired
correctly.
A-tL
Empty-water pre-
alarm
The pumping pool has no water. If you have configured the empty-
water pre-alarm function, the device
automatically stops when the pre-
alarm elapsed. Otherwise, check
whether terminals are wired
correctly.