Goodrive170-PV Series Solar Pump Inverter Installation guidelines
-8-
inverter. Otherwise, the inverter may be damaged.
The relative humidity (RH) of the air is less than 90%.
Condensation is not allowed.
-40°C–70°C, with the air temperature change rate less than 1°C/minute.
Install the inverter in a place:
Away from electromagnetic radiation sources.
Away from oil mist, corrosive gases and combustible gases.
Without the chance for foreign objects such as metal powder, dust,
oil and water to fall into the inverter (do not install the inverter onto
combustible objects such as wood).
Without radioactive substances and combustible objects.
Without hazard gases and liquids.
With low salt content.
Without direct sunlight.
Lower than 1000m;
When the altitude exceeds 1000m, derate 1% for every increase of
1˚C.
When the altitude exceeds 3000m, consult the local INVT dealer or
office.
Max. vibration acceleration: 5.8m/s
2
(0.6g).
Install the inverter vertically to ensure good heat dissipation
performance.
Note:
The inverter must be installed in a clean and well-ventilated environment based on
the IP level.
The cooling air must be clean enough and free from corrosive gases and conductive
dust.
3.1.2 Installation direction
The inverter can be installed on the wall or in a cabinet.
The inverter must be installed vertically. Check the installation position according to
following requirements. See Appendix D “Dimension drawings”.