Goodrive170-PV Series Solar Pump Inverter Function parameter list
-23-
Function
code
Name
Description
Default
Modify
parameter because reverse running is not
allowed in water pump application
scenarios.
2: Disable reverse running. It can be used in
some special scenarios where reverse
running is disallowed.
P00.15
Motor
parameter
autotuning
0: No operation
1: Rotary autotuning
Comprehensive motor parameter autotuning.
It is recommended to use rotating autotuning
when high control accuracy is needed.
2: Static autotuning 1
Used in scenarios where the motor cannot
be disconnected from load.
3: Static autotuning 2
Empty-load current and mutual inductance
are not autotuned.
0
P00.18
Function
parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
Note:
After the selected operation is
performed, the function code is
automatically restored to 0.
Restoring the default values may delete
the user password. Exercise caution
before using this function.
0
P01 group Start and stop control
Function
code
Name
Description
Default
Modify
P01.08
Stop mode
0: Decelerate to stop. When a stop
command takes effect, the inverter lowers
output frequency based on the DEC mode
and the defined DEC time; when the
frequency drops to 0Hz, the inverter stops.
1: Coast to stop. When a stop command
0