Note: Max. output frequency ≥ Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00Hz–P00.04 (Upper limit of
running frequency)
ACC time means the time needed if the
inverter speeds up from 0Hz to the max.
output frequency (P00.03).
DEC time means the time needed if the
inverter speeds down from the max. output
frequency (P00.03) to 0Hz.
The inverter has four groups of ACC/DEC
time, which can be selected by P05. The
factory default ACC/DEC time of the inverter
is the first group.
Setting range of P00.11 and P00.12: 0.0–
3600.0s
0: Run at the default direction. The inverter
runs in the forward direction. FWD/REV is
off.
1: Run at the opposite direction. The inverter
runs in the reverse direction. FWD/REV is
on.
Modify P00.13 to shift the rotation direction of
the motor. This effect equals to the shifting
the rotation direction by adjusting either two
of the motor lines (U, V and W). The motor
rotation direction can be changed by
QUICK/JOG on the keypad. For details,
refer to parameter P07.02.
Note:
When the parameter is restored to the
default value, the motor’s running
direction is restored to the default one.
Exercise caution before using this
function if the change of motor rotation
direction is disallowed after
commissioning.
Do not change the setting of the