GD200A series VFD Function parameters
-56-
Function
code
Name
Description
Default
value
Modify
(the rated voltage of the motor)
Vmax
Vmin
Vset
t1
t2
T
t1=P04.29
t2=P04.30
P04.33
Flux weakening
coefficient at
constant power
Used to adjust the output voltage of VFD in
SVPWM mode during flux weakening.
Note: Invalid in constant-torque mode.
Output Voltage
Output frequency
(P04.33-1.00)*Vb
out
b
V
V
f 2f
b
b
Setting range of P04.33: 1.001.30
1.00
P04.34
Reserved
P05 Group Input terminals
Function
code
Name
Description
Default
value
Modify
P05.00
HDI input
0: HDI is high pulse input. See P05.50P05.54
1: HDI is switch input
0
P05.01
S1 terminal
function
selection
0: No function
1: Forward rotation
2: Reverse rotation
3: 3-wire control
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting(UP)
11: Decreasing frequency setting(DOWN)
12: Cancel the frequency change setting
13: Shift between A setting and B setting
14: Shift between combination setting and A
setting
15: Shift between combination setting and B
1
P05.02
S2 terminal
function
selection
4
P05.03
S3 terminal
function
selection
7
P05.04
S4 terminal
function
selection
0
P05.05
S5 terminal
function
selection
0