Goodrive350-19 series VFD     Operating 
- 194 - 
Directdeceleration positioning 
Frequency
Running command
Photoelectric switch
arrival signal
Cyclic positioning
enable signal
Positioning completion
signal
Constant speed+
deceleration positioning
Directdeceleration positioning 
Constant speed+
deceleration positioning
Time
 
Step 1–4: These four steps are the Same as the first four steps of the commissioning procedures for 
closed-loop vector control, which aim to fulfill the control requirements of closed-loop vector control. 
Step 5: Set P21.00=0021 to enable photoelectric switch positioning, the photoelectric switch signal 
can  be  connected  to  S8  terminal  only,  and  set  P05.03=43,  meanwhile,  set  P21.17,  P21.11  and 
P21.12  (set  positioning  displacement)  based  on  actual  needs;  set  P21.21  (deceleration  time  of 
positioning), however, when present running speed is too fast or the set positioning displacement is 
too  small,  the  deceleration time of positioning  will be  invalid, and it  will  enter direct deceleration 
positioning mode. 
Step 6: Cyclic positioning 
After positioning is done, the motor will stay in current position. You can set cyclic positioning through 
input terminal function selection (55: enable cyclic digital positioning) in P05 group; when the terminal 
receives cyclic positioning  enable signal (pulse signal), the motor will  continue running in the set 
speed as per the speed mode and re-enter positioning state after encountering photoelectric switch. 
Step 7: Hold positioning 
The  position  loop  gain  during  positioning  is  P21.03;  while  the  position  loop  gain  in 
positioning-completion-hold state is P21.02. In order to keep sufficient position-hold force and ensure 
no system oscillation occurred, adjust P03.00, P03.01, P20.05 and P21.02. 
6.5.18 Fault handling 
GD350-19  series  VFD  provides  abundant  information  concerning  fault  handling  for  easy 
maintenance.