VS070QS-1618MDM1 Integrated Machine Mechanical installation
202403 (V1.0) 25
power supply terminal to the ground. It is recommended that you use
connection wires of AWG12 to AWG16 and try to shorten the wires.
It is recommended that you configure independent grounding and keep the
grounding cables away from those of other devices (especially those generating
strong interference), as shown in the following figure.
3.1.3.1 Cable specification
For the wiring of the PLC, it is recommended that you use multi-stranded copper
wire and prepare insulated terminals to ensure the wiring quality. The following
table describes the recommended wire cross-sectional areas and models.
Cable
Cross-sectional
area of wire
Wire model
Cable lug and heat-shrink tube
Power
cable
1.0–2.0mm²
AWG12, 18
H1.5/14 preinsulated tube-like terminal,
or hot tin-coated cable terminal
Grounding
cable
2.0mm²
AWG12
H2.0/14 preinsulated tube-like terminal,
or hot tin-coated cable terminal
Input
signal
cable (X)
0.8–1.0mm²
AWG18, 20
UT1-3 or OT1-3 solderless lug
Ø3 or Ø4 heat shrinkable tube
Output
signal
cable (Y)
0.8–1.0mm²
AWG18, 20
Fix the processed cable terminals onto the wiring terminals of the PLC by using
screws. Pay attention to the positions of the screws. The tightening torque for the
screws is 0.5 to 0.8 Nm, which can be used to complete reliable connection without
damaging the screws.