VS070QS-1618MDM1 Integrated Machine Product overview
202403 (V1.0) 18
Reverse voltage = (5–10) * Load
voltage
Forward current > Load current
The rated voltage shall match with
the load.
Electrostatic capacity = 0.1μF
Resistance value = 100–200Ω
2.3.7 Analog input/output characteristics
2.3.7.1 Input connection instance of analog signal
For analog input, it is recommended to use shielded twisted-pair cables. The
cable shall be kept away from power cables or other cables that may cause
electrical interference.
If there is fluctuation in input signals or electrical interference during the
external wiring, a smoothing capacitor (0.1μF–0.47μF/25 V) is recommended.
If the current channel uses the power input, the voltage and current input ports
should be shorted.
Analog power supply not only can use 24 V DC power supply output by the main
module, but can use other power supplies that meet the requirements.
Do not use the unconnected pin on the user terminals.