VS070QS-1618MDM1 Integrated Machine Analog input/output
202403 (V1.0) 49
2. Connect the current mode analog output D/A channel 1 to the current mode
analog input A/D channel 1. For details, see 2.3.7 Analog input/output
characteristics.
First, set SM178 (D/A channel 1 enabling flag) to ON, SM179 (D/A channel 1
output mode flag) to ON and SD178 to 6000.
Then, set SM172 (A/D channel 1 enabling flag) to ON and SM173 (A/D channel 1
output mode flag) to OFF, you can see that the current output of D/A channel 1
has been given to the current input of A/D channel 1, i.e., SD172 = 6037.