M3.3.1. TMAX °C
| Factory setting 80 | Min. 65 | Max. 80 | +/- 5 |
800
tmax
The LED indicator flashes yellow rapidly.
Setting or adjusting the maximum stored water temperature during
SMART CONTROL.
M3.3.2. TMIN °C
| Factory setting 55 | Min. 55 | Max. 60 | +/- 1 |
550
tmin
The LED indicator flashes yellow rapidly.
Setting or adjusting the minimum stored water temperature during
SMART CONTROL.
M3.3.3. ERROR RESET
| Factory setting 0 | 0/1 | +/- |
0
ERROR
The LED indicator flashes yellow rapidly.
Activating the ERROR RESET function clears the history of the fault
messages.
After the history is cleared, the function is automatically disabled
and the water heater restarts in STANDBY mode.
The heater mode must be changed to ON via the BOIL setting.
● 0 - The function is disabled.
● 1 - Immediate, one-time enabling of the function.
Tip
The ERROR RESET function can also be performed during error
notification in the operational status by pressing the ↺ button
for approximately five seconds.