Prophi
®
12R / 12 RS
32
PROGRAMMING
1 LINE VOLTAGE
230.0 V-L/N
2 CURRENT [1]
200.0 A
3 REACTIVE POWER
88.88 kvar
4 ACTIVE POWER
88.88 kW
5 APPARENT POWER
88.88 kVA
6 DIFF. REACT POWER
88.88 kvar
7 FREQUENCY
50.0 Hz
1 I-CT PRIMARY
[ 1000 ] A / X A
19 I-CT PRIMARY
[ 1000 ] A / X
2 I-CT PRIMARY
[ 1000 ] A / X
0 LANGUAGE
[ ENGLISH ]
1 CURRENT TRANSF.
[ KNOWN ]
AUTO-INIT*
[ NO ]
2 I-CT SECONDARY
20 I-CT SECONDARY
3 I-CT SECONDARY
8 MEAS. VOLTAGE
[ 230 ] V - L/N
9 V - CT RATIO
[ NO ]
10 SWITCH-IN TIME
[ 40 ] sec.
26 SWITCH-IN TIME
[ 40 ] sec.
11 SWITCH-OFF TIME
[ 40 ] sec.
27 SWITCH-OFF TIME
[ 40 ] sec.
12 DISCHARGE TIME
[ 60 ] sec.
28 DISCHARGE TIME
[ 60 ] sec.
29 Q - OFFSET
[ NO ]
13 ALARM TEMP.
[ 55 °C ]
14 ALARM RELAY [3]
[ ERROR inverse]
15 FAN TEMP.
[ 30 °C ]
8 TEMPERATURE [1]
25 °C
9 HARMONICS [ 3. ]
V: 0.5% - I: 0.1%
10 HARMONICS THD rel.
V: 0.5% I: 0.3%
11 SYSTEM-POWER
88.88 kvar
12 ENERGY [1]
88.88 kWh ( + )
13 DATE - TIME [1]
06.11.2015 - 10:13:40
18 CONTRAST
* * * * * [ 4 ] * * * * *
14 SOFTWARE
VERSION ....
17 HARMONICS
[ 3. 5. 7. - 19.]
16 HARMONICS
THD-I [ -,- ] %
16 HARMONICS
THD-V [ 7 ] %
BASIC SETTINGS
RESET - NO -
Changing
of values
by buttons:
After 60 sec. without pressing
any button, automatic change
to auto-mode
Settings shown with grey background
colour are active only in case
of certain other settings.
If not needed they are not displayed.
BACK
4 CONTROL SERIES [1]
[1 1 1 1 1 1 1 1 1 1 1 1]
22 CONTROL SERIES [1]
[1 1 1 1 1 1 1 1 1 1 1 1]
5 CONTROL MODE [2]
[ INTELLIGENT ]
23 CONTROL MODE [2]
[ INTELLIGENT ]
7 TARGET
cos Phi [ 0.98 IND ]
25 TARGET
cos Phi [ 0.98 IND ]
6 POWER 1. STAGE
[ 25 ]. 00 kvar
24 POWER 1.STAGE
[ 25 ]. 00 kvar
3 END STOPP [12]
21 END STOPP [12]
4 POWER 1. STAGE
[ 25 ].00 kvar
TEST 1...3
(automatic TEST RUN)
AUTO MODE
---------------
cos
j 1.000 IND
BACK TO 1
1000 A / [5] A
1000 A / [5] A
1000 / [5] A
- 31 -
1 2 3 4 5 6 7 8 9 10 11 12
2
2
2
2
2
2
2
2
2
2
By pressing the cursor buttons (up / down)
the stage display mode can be changed
* AUTO INIT exists only,
if in „ExpertMode 2":
„2 Auto-Init Error = YES“