66
UMG 104
Temperature measurement input
Update time : approx 200 ms
Connectable sensors : PT100, PT1000, KTY83, KTY84
Total burden (sensor + cable) : max 4 kohm
Sensor type Temperature range Resistance range Measurement
uncertainty
KTY83 -55 ° .. +175 °C 500 ohm .. 2.6 kohm ± 1.5% rng
KTY84 -40 ° .. +300 °C 350 ohm .. 2.6 kohm ± 1.5% rng
PT100 -99 ° .. +500 °C 60 ohm .. 180 ohm ± 1.5% rng
PT1000 -99 ° .. +500 °C 600 ohm .. 1,8 kohm ± 1.5% rng
rng
= measuring range
Cable length : up to 30 m unshielded
: greater than 30 m shielded
Connectable conductors
Solid core, multi-core, flexible core : 0.08 - 1.5 mm
2
Pin-end connector, wire end ferrules : 1 mm
2
, only one conductor may be connected
per terminal connection!