QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 71
MODE VALUES: (Continued)
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Value Code
4457 N44:57 44458 R Sequencing Enable - System 2
0 = Disabled
1 = Enabled
4467 N44:67 44468 R Sequencing – Sys. 2 Comp 1 Comp Status
0 = Off
1 = Running
20 = Starting
30 = Stopping
31 = Stopping - High Capacity
32 = Stopping - Pumpdown
4468 N44:68 44469 R Sequencing – Sys. 2 Comp 2 Comp Status
4469 N44:69 44470 R Sequencing – Sys. 2 Comp 3 Comp Status
4470 N44:70 44471 R Sequencing – Sys. 2 Comp 4 Comp Status
4471 N44:71 44472 R Sequencing – Sys. 2 Comp 5 Comp Status
4472 N44:72 44473 R Sequencing – Sys. 2 Comp 6 Comp Status
4473 N44:73 44474 R Sequencing – Sys. 2 Comp 7 Comp Status
4474 N44:74 44475 R Sequencing - Sys 2 Comp 8 Comp Status
4483 N44:83 44484 R Sequencing – Sys. 3 Comp 1 Comp Mode
0 = Manual
1 = Automatic
2 = Remote - Communications
3 = Remote - IO
5 = Remote – Sequencing
4484 N44:84 44485 R Sequencing – Sys. 3 Comp 2 Comp Mode
4485 N44:85 44486 R Sequencing – Sys. 3 Comp 3 Comp Mode
4486 N44:86 44487 R Sequencing – Sys. 3 Comp 4 Comp Mode
4487 N44:87 44488 R Sequencing – Sys. 3 Comp 5 Comp Mode
4488 N44:88 44489 R Sequencing – Sys. 3 Comp 6 Comp Mode
4489 N44:89 44490 R Sequencing – Sys. 3 Comp 7 Comp Mode
4490 N44:90 44491 R Sequencing – Sys. 3 Comp 8 Comp Mode
4491 N44:91 44492 R Sequencing – Sys. 3 Comp 1 Capacity Mode
0 = Manual
1 = Automatic
2 = Remote - Communications
3 = Remote - IO
4 = Remote - 4-20 Input
5 = Remote – Sequencing
4492 N44:92 44493 R Sequencing – Sys. 3 Comp 2 Capacity Mode
4493 N44:93 44494 R Sequencing – Sys. 3 Comp 3 Capacity Mode
4494 N44:94 44495 R Sequencing – Sys. 3 Comp 4 Capacity Mode
4495 N44:95 44496 R Sequencing – Sys. 3 Comp 5 Capacity Mode
4496 N44:96 44497 R Sequencing – Sys. 3 Comp 6 Capacity Mode
4497 N44:97 44498 R Sequencing – Sys. 3 Comp 7 Capacity Mode
4498 N44:98 44499 R Sequencing – Sys. 3 Comp 8 Capacity Mode
4507 N45:07 44508 R Sequencing Enable - System 3
0 = Disabled
1 = Enabled
4517 N45:17 44518 R Sequencing – Sys. 3 Comp 1 Comp Status
0 = Off
1 = Running
20 = Starting
30 = Stopping
31 = Stopping - High Capacity
32 = Stopping - Pumpdown
4518 N45:18 44519 R Sequencing – Sys. 3 Comp 2 Comp Status
4519 N45:19 44520 R Sequencing – Sys. 3 Comp 3 Comp Status
4520 N45:20 44521 R Sequencing – Sys. 3 Comp 4 Comp Status
4521 N45:21 44522 R Sequencing – Sys. 3 Comp 5 Comp Status
4522 N45:22 44523 R Sequencing – Sys. 3 Comp 6 Comp Status
4523 N45:23 44524 R Sequencing – Sys. 3 Comp 7 Comp Status
4524 N45:24 44525 R Sequencing – Sys. 3 Comp 8 Comp Status
4533 N45:33 44534 R Oil Pump Mode
0 = Manual