QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 72
MODE VALUES: (Continued)
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Value Code
4534 N45:34 44535 R Screen Saver
0 = Disabled
1 = Enabled
4539 N45:39 44540 R Starter Alarms
4540 N45:40 44541 R Starter Trips
4547 N45:47 44548 R Input Module Capacity Mode Selection
0 = Disabled
1 = Enabled
4548 N45:48 44549 R Permissive Start Enable
0 = Disabled
1 = Starting
2 = Always
4549 N45:49 44550 R PLC Interlock Enable
0 = Disabled
1 = Enabled
4550 N45:50 44551 R Remote Enable Output
0 = Disabled
1 = Compressor Mode: Remote I/O
2 = Compressor Mode: Remote I/O
and Capacity Mode: Remote I/O
3 = Compressor Mode: Remote I/O
and Capacity Mode: Remote 4-20
4551 N45:51 44552 R Oil Log Mode
0 = Disabled
1 = Enabled
4566 N45:66 44567 R Communications Unit Flag
0 = Celsius / PSIA
1 = Panel Units
4690 N45: 44691 R Discharge Butterfly Valve Control
0 = Disabled
1 = Enabled
4691 N45: 44692 R Discharge Butterfly Valve Lock Open Flag
0 = No
1 = Yes
4692 N45: 44693 R Low Discharge Pressure Shutdown Enable
0 = Disabled
1 = Enabled
4693 N45: 44694 R EZ Cool LIOC Control
0 = Disabled
1 = Running
2 = Always
4694 N45: 44695 R Liquid Injection Closed Warning Flag
0 = False
1 = True
4696 N45: 44697 R Separator Condensing Safeties Enable
0 = Disabled
1 = Enabled
4697 N45: 44698 R Wet Bulb Control
0 = Disabled
1 = Enabled
4698 N45: 44699 R Wet Bulb Refrigerant
0 = R22
6 = R134A
12 = R717
14 = R744