Table 11: FX-PCG26 technical specifications
Power Consumption 20 VA maximum for FX-PCG2621 (with integral display) only
Note: VA rating does not include any power supplied to the
peripheral devices connected to Binary Outputs (BOs) or
Configurable Outputs (COs), which can consume up to 12 VA
for each BO or CO; for a possible total consumption of an
additional 84 VA (maximum).
Ambient Conditions Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH
noncondensing
Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH
noncondensing
Addressing BACnet
®
MS/TP: DIP switch set; valid field controller device
addresses 4–127 (Device addresses 0–3 and 128–255 are
reserved and not valid controller addresses.)
N2: DIP switch set; valid controller device addresses 1–255
Communications Bus RS-485, field selectable between BACnet MS/TP and N2
communications:
3-wire FC Bus between supervisory controller and field
controllers.
4-wire SA Bus between field controller, network sensors, and
other sensor/actuator devices, includes a lead to source 15 VDC
supply power (from field controller) to bus devices.
Processor H8SX/166xR Renesas
®
32-bit microcontroller
Memory 640 KB flash memory and 128 KB RAM
Input and Output Capabilities FX-PCG26 Series:
6 - Universal Inputs: Defined as 0–10 VDC, 4-20 mA, 0–600k
ohm, or Binary Dry Contact
2 - Binary Inputs: Defined as Dry Contact Maintained or Pulse
Counter/Accumulator Mode
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal
or external source power)
4 - Configurable Outputs: Defined as 0–10 VDC
2 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA
Analog Input/Analog Output
Resolution and Accuracy
Input: 16-bit resolution
Output: 16-bit resolution, +/- 200 mV accuracy in 0-10 VDC
applications
Terminations Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable
Screw Terminal Blocks
SA Bus Port: RJ-12 6-Pin Modular Jacks
33FX-PCG26 General Purpose Programmable Controller Installation Instructions