FX-PCG2511 and FX-PCG26 point type counts
The following table shows the different point types and counts available in the FX-PCG2511 and FX-
PCG26 Series controllers.
Table 3: FX-PCG2511 and FX-PCG26 point type counts per model
Point types Signals accepted FX-PCG2511
(Asia/Europe only
model)
FX-PCG26
Universal Input (UI) Analog Input, Voltage Mode, 0–
10 VDC
Analog Input, Current Mode, 4–
20 mA
Analog Input, Resistive Mode,
0–2k ohm, RTD (1k NI [Johnson
Controls], 1k PT, A99B SI), NTC
(10k Type L, 2.252k Type 2)
Binary Input, Dry Contact
Maintained Mode
4 (Does not support
Current Mode)
6
Binary Input (BI) Dry Contact Maintained Mode
Pulse Counter/Accumulator
Mode (High Speed), 100 Hz
6 2
Analog Output (AO) Analog Output, Voltage Mode,
0–10 VDC
Analog Output, Current Mode,
4–20 mA
2 (Voltage Only) 2
Binary Output (BO) 24 VAC Triac 2 (Ext Power only) 3
Configurable Output
(CO)
Analog Output, Voltage Mode,
0–10 VDC
Binary Output Mode, 24 VAC
Triac
2 4
FX-PCG2511 and FX-PCG26 I/O wiring ratings and
requirements table
The following table shows the input/output requirements and ratings for the FX-PCG2511 and FX-
PCG26 Series controllers.
17FX-PCG26 General Purpose Programmable Controller Installation Instructions