5-18
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents
26 CC Not Prepared - - NotUsed(Useas00conditions)
27 Cd Not Prepared - - NotUsed(Useas00conditions)
28 CE Not Prepared - - NotUsed(Useas00conditions)
29 CF ChangeofLouverSwingAngle
00
01
02
Standard(7-StepOperation)
ColdDraftPrevention
(5Steps:lower2stepscutoff)
HighCeiling(higher2stepscutoff)
30 d1 PowerSupplyON/OFF1
00
01
NotAvailable
Available
31 d2 Not Prepared - - Not Used
32 d3 PowerSupplyON/OFF2
00
01
NotAvailable
Available
33 d4 Not Prepared - - NotUsed(Useas00conditions)
34 d5
PreventionforHeatingDischargeAir
Temp.Decrease
00
01
NotAvailable
Available
35 d6 Not Prepared - - NotUsed(Useas00conditions)
36 d7 Not Prepared - - Not Used
37 E1 Not Prepared - - NotUsed(Useas00conditions)
38 E2 Not Prepared - - NotUsed(Useas00conditions)
39 E3 Not Prepared - - NotUsed(Useas00conditions)
40 E4 Not Prepared - - NotUsed(Useas00conditions)
41 E5 Not Prepared - - NotUsed(Useas00conditions)
42 E6
IndoorFanOperationTimeAfter
CoolingOperationStoppage
00
01
02
NotAvailable
60min.
120min.
43 E7 Not Prepared - - NotUsed(Useas00conditions)
44 E8
FanOperationControlduring
HeatingThermo-OFF
00
01
NotAvailable(LOW)
SLOW
45 E9 Not Prepared - - NotUsed(Useas00conditions)
46 EA Not Prepared - - NotUsed(Useas00conditions)
47 Eb
FanOperationControlduring
CoolingThermo-OFF
00
01
02
NotAvailable
LOW
SLOW
48 EC
ForcedThermo-ONStoppageduring
Cooling
00
01
NotAvailable
Available
49 Ed Not Prepared - - NotUsed(Useas00conditions)
50 EE Not Prepared - - NotUsed(Useas00conditions)
51 EF
AutomaticFanSpeedControl
(High2)
00
01
NotAvailable
Available
52 F0 Not Prepared - - Not Used
53 F1 AutomaticOFFTimerSetting
*Donotsetthefunctions“0C”~“0F”
when2(two)wiredcontrollersare
usedinthesamecontrollergroup.
×
00
01
02
23
24
0A
0B
0C
0D
0E
0F
No Function
OFFTimerby1hr
OFFTimerby2hrs
OFFTimerby23hrs
OFFTimerby24hrs
OFFTimerby30min.
OFFTimerby90min.
OFFTimerby40min.
OFFTimerby45min.
OFFTimerby50min.
OFFTimerby55min.
}
Donotsetthemwhen
twowiredcontrollers
are used.
54 F2 WiredControllerMain-SubSetting
×
00
01
Main
Sub
55 F3
AutomaticResetofSetting
Temperature(*2)
×
00
01
NotAvailable
Available