EasyManua.ls Logo

Johnson Controls HICM008B21S - 5.4.1.5 Remote Cooling;Heating Change; External Signal for Mode Change

Johnson Controls HICM008B21S
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM-18003
5-13
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
NOTES:
1.WiredControllerisrequiredforthisfunction.
2.RefertoTable5.1fordetailsoftherequiredcomponents.
3.Ifmultipleindoorunitsareconnectedtothesamecommunicationcableforwiredcontroller,inputthe
signaltoanyoftheseindoorunits.
4.Whenthecommunicationcableisnotusedinthetwin,tripleandquadcombinationsforsimultaneous
operation,setthisfunctiononlytothemainindoorunit.
Indoor Unit PCB
Wiring Diagram Example
(Example: Remote Cooling/Heating Change is set to terminals 1 and 2 of CN3.)
CN3
X1
3P Connector
3
2
1
2
1
COOLHEAT
X1
Power
Source
Signal to terminals 1 & 2 of CN3
Heat
Cool
Heat
Cool
Operation Mode of Unit
Control by Wired Controller (Cool)
Time Chart
(Example: Remote Cooling/Heating Change is set to terminals 1 and 2 of CN3.)
Control by Wired Controller (Heat)
5.4.1.5 RemoteCooling/HeatingChange[InputSetting:Code(07)]
Thecoolingorheatingoperationmodecanbechangedbygivingacontactsignalfromtheoutsidetothe
unit.SetthisfunctiontoCN3withawiredcontrolleraccordingtoSection5.4.2.1“FunctionSelectionItem.”
ThisfunctiondetectsONtoOFFtransitionandOFFtoONtransition.Ofthecommandsbythissignaland
awiredcontroller,thecommandgivenlaterispreferentiallyexecuted.Anexampleofbasicwiringandtime
chartisshownbelow.

Table of Contents

Related product manuals