EasyManua.ls Logo

Johnson Controls HICM008B21S - 5.4.2 Function Setting Overview; 5.4.2.1 Function Selection Item List

Johnson Controls HICM008B21S
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM-18003
5-17
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.2.1 FunctionSelectionItem
5.4.2 FunctionSetting
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents
1 b1
CancellationofHeating
TemperatureCompensation
duetoUnevenHeatLoad
00
01
02
03
04
Standard(SetTemp.+7
o
F(+4
o
C))
Removal(SetTemp.)
SetTemp.+3
o
F(+2
o
C)(*1)
SetTemp.+5
o
F(+3
o
C)
SetTemp.+2
o
F(+1
o
C)
2 b2
CirculatorFunctionduring
HeatingThermo-OFF
00
01
NotAvailable
Available
3 b3 Not Prepared - - NotUsed(Useas00conditions)
4 b4 ChangeofFilterCleaningTime -
00
01
02
03
04
Standard1,200hrs(Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5 b5 FixingofOperationMode
×
00
01
Standard
Fixed
6 b6 FixingofSettingTemperature
×
00
01
Standard
Fixed
7 b7
FixingofOperationas
ExclusiveCoolingUnit
×
00
01
Standard
Fixed
8 b8 AutomaticCOOL/HEATOperation
×
00
01
NotAvailable
Available
9 b9 FixingofFanSpeed
×
00
01
Standard
Fixed
10 bA Not Prepared - - Not Used
11 bb
CoolingTemperatureCompensation
duetoUnevenHeatLoad
×
00
01
02
Standard(NoCompensation)
SetTemp.–2
o
F(–1
o
C)
SetTemp.–3
o
F(–2
o
C)
12 bC Not Prepared - - NotUsed(Useas00conditions)
13 bd Not Prepared - - NotUsed(Useas00conditions)
14 bE Not Prepared - - NotUsed(Useas00conditions)
15 C1 Not Prepared - - NotUsed(Useas00conditions)
16 C2 Not Prepared - - Not Used
17 C3 Not Prepared - - Not Used
18 C4 Not Prepared - - Not Used
19 C5
Hi Speed
(ExceptforHiSpeedduringHeating
Thermo-OFF)
00
01
02
NotAvailable
Hi Speed 1
Hi Speed 2
20 C6
HiSpeedduringHeatingThermo-
OFF
00
01
NotAvailable
Available
21 C7
CancelingofEnforced3Minutes
MinimumOperationTimeof
Compressor
00
01
Standard
Cancellation
22 C8 ThermistorofWiredController(*6)
00
01
02
00
01
02
<IfWiredControllerThermistorisSelected˃
NotAvailable
ControlbyThermistorofWiredController
ControlbyAverageValueofIndoorSuction
ThermistorandThermistorofWiredController
<IfRemoteSensorisSelected˃
ControlbyAverageValueofIndoorSuction
ThermistorandRemoteSensor
ControlbyRemoteSensor
Sameas"00"
23 C9 Not Prepared - - Not Used
24 CA Not Prepared - - Not Used
25 Cb SelectionofForcedStoppageLogic
×
00
01
ForcedStoppageInput:AContact
ForcedStoppageInput:BContact

Table of Contents

Related product manuals