EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(22) Thermistor of Wired Controller (C8)
Thisfunctionisutilizedtocontroltheunitbythebuilt-inthermistorofthewiredcontroller(wired
controllerthermistor)insteadoftheinletairthermistor.
Setthisfunctionat“01”or“02”whenutilizingthisfunction.
However,evenifthisfunctionissetat“01”or“02”,ifthedetectingtemperatureisabnormalduetothe
failureofthethermistorofthewiredcontroller,etc.,thecontrolischangedtotheinletairthermistorof
theindoorunitautomatically.
TheoptionalpartRemoteSensor(THM-R2A)willcontroltheunitwhenitisconnected.
(30) Power Supply ON/OFF 1 (Automatic Operation when Power Supply Is ON) (d1)
Thisfunctionisutilizedtorun/stoptheunitbyturningON/OFFthepowersupply.
Whenthisfunctionisutilizedintheconditionthatthereisnopersontooperatetheunit,monitorthe
systemforpotentialunitfailure.
NOTE:
TheunitwillbestoppedevenwhenthepowersupplyisturnedON/OFFduetopowerfailure.Ifpower
failureoccursduringthestoppageoftheunit,theoperationisrestartedafterthepowersupplyis
restored.
(31) Not Prepared (d2)
(26) Not Prepared (CC)
(27) Not Prepared (Cd)
(28) Not Prepared (CE)
(29) Change of Louver Swing Angle (CF)
Thisfunctionisutilizedtothechangelouverswingangle.
Setting
Condition
LouverSwingAngle
(AirDischargeAngle)
Purpose
00 7 Steps Standard Operation
01 Lower2StepsareCut DraftPrevention
02 Higher2StepsareCut ForHighCeiling
NOTE:
Whenchangingthesetting,turnOFFthepowersupplyor
allowthelouvertomakeonecompleteswingfullyintheauto
swingmodetovalidatethesetting.
Setting
Condition
Logic of
Contact
Sequence
Activation
00 A Contact Normal
Forced
Stoppage
01 B Contact Normal
Forced
Stoppage
Contact "Close"Contact "Open"
Indoor
PCB
Indoor
PCB
A
ir
Discharge
A
ngle
(23) Not Prepared (C9)
(24) Not Prepared (CA)
(25) Selection of Forced Stoppage Logic (Cb)
Thisfunctionisutilizedtoselectthelogicofthecontactforforcedstoppagesignalinput.
Thesettingconditionandthelogicofthecontactareasshownbelow.
SelectedThermistor SettingCondition ControlledIndoorTemp.
ThermistorofWiredController
00 IndoorSuctionThermistor
01 ThermistorofWiredController
02
AverageValueofIndoorSuctionThermistorand
ThermistorofWiredController
RemoteSensor
00
AverageValueofIndoorSuctionThermistorand
RemoteSensor
01 RemoteSensor
02 Sameas"00"