TROUBLESHOOTING
1: Refer to Section 3.1.4 (3) above for details.
Cause Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
Float Switch
Failure of
Float Switch
Failure of
Drain Pump
Contact Failure
Incorrect Connection
Failure
Contact Failure
Incorrect Connection
Failure
Check drain pan.
Check drainage by
pouring water.
Check continuity
when drain level is low.
Measure resistance
with a tester.
Measure resistance
with a tester.
Measure voltage
between CN36 terminals
with a tester.
Check connection.
Check connection.
High Drain
Level
Clogging of
Drainage
Up-Slope
Drain Piping
Remove foreign particles
clogging drain pipe.
Replace float switch
if faulty.
Replace drain pump
if faulty.
Replace and tighten
connector.
Replace and tighten
connector.
Repair connection.
Repair connection.
Check PCB in
Self-Checking Mode.
1
Replace it if faulty.
Failure of
Indoor Unit PCB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls HICM008B21S and is the answer not in the manual?

Johnson Controls HICM008B21S Specifications

General IconGeneral
BrandJohnson Controls
ModelHICM008B21S
CategoryAir Conditioner
LanguageEnglish

Related product manuals