Multipliers for determining the performance with other
indoor sections
Note: For dry bulb temperatures different than those listed (between 73°F to 87°F), sensible
capacity increases by 1060 Btu/h per 1000 CFM per degree above the listed temperature and
decreases by 1060 Btu/h per 1000 CFM per degree below the listed temperature.
Cool multiplier air handler - 3 ton
Table 30: Cool multiplier air handler - 3 ton
Air handler model Indoor coil model Total capacity Sensible capacity kW
— XAFB36D 1.00 1.00 1.00
— XAFB36E 1.00 0.99 1.00
— XAFC36D 1.00 1.00 1.00
— XAFC42E 1.00 1.00 1.00
— XAFD42E 1.00 1.01 1.00
— XAHC36D 1.00 1.00 1.00
— XAHC42E 1.00 1.00 1.00
— XAHD42E 1.00 1.01 1.00
— XAUB36D 1.00 1.00 1.00
— XAUC42E 1.00 1.00 1.00
JHETB36DBCS2N1 — 1.02 1.02 0.97
JHETC36DBCS2N1 — 1.02 1.01 0.95
JHVTB36DBCC2N1 — 1.00 0.95 0.94
JHVTC36DBCC2N1 — 1.02 0.97 0.93
JMET12BS2N1A XAFB36D 1.02 1.01 0.95
JMET12BS2N1A XAFB36E 1.02 1.00 0.95
JMET12BS2N1A XAUB36D 1.02 1.01 0.95
JMET12BS4N1A XAFB36D 1.02 1.02 0.97
JMET12BS4N1A XAFB36E 1.02 1.03 0.97
JMET12BS4N1A XAUB36D 1.02 1.02 0.97
JMET12CS2N1A XAFC36D 1.02 0.98 0.95
JMET12CS4N1A XAFC36D 1.01 0.95 0.94
JMET12CS4N1A XAFC42E 1.01 0.95 0.92
JMET12CS4N1A XAHC36D 1.00 0.93 0.94
JMET12CS4N1A XAHC42E 1.00 0.93 0.94
JMET12CS4N1A XAUC42E 1.01 0.95 0.92
JMVT12BC2N1A XAFB36D 1.00 0.93 0.94
JMVT12BC2N1A XAFB36E 1.00 0.93 0.94
JMVT12BC2N1A XAUB36D 1.00 0.93 0.94
JMVT16CC2N1A XAFC42E 1.02 0.97 0.93
JMVT16CC2N1A XAHC42E 1.02 0.97 0.93
JMVT16CC2N1A XAUC42E 1.02 0.97 0.93
Cool multiplier furnace - 3 ton
Table 31: Cool multiplier furnace - 3 ton
Furnace model Indoor coil model Total capacity Sensible capacity kW
TL8E060A12UH11 XAFB36D 1.01 0.98 1.01
TL8E060A12UH11 XAFB36E 1.01 0.98 1.01
TL8E060A12UH11 XAUB36D 1.01 0.98 1.01
TL8E080C16UH11 XAFC36D 1.01 0.98 0.96
TL8E080C16UH11 XAFC42E 1.01 0.99 0.97
TL8E080C16UH11 XAFD42E 1.00 0.98 0.98
Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase106
Johnson Controls Ducted Systems