TEC3000 Series Networked and Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with Dehumidification Capability
Quick Start Guide
1
Refer to the QuickLIT website for the most up-to-date version of this document.
North American emissions compliance
United States
Canada
Installation
Parts included
One TEC3000 Series Thermostat Controller with integral mounting base
One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series Thermostat Controller:
On a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature, allowing
for vertical air circulation to the TEC
Away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, stairwells, and
from
b
ehind doors
Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
In a clear path between the integrated passive infrared (PIR) occupancy sensor (if equipped) and the spac
e
be
ing monitored
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
TEC3000 Series Networked and Wireless Proportional Fan
Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability
Quick Start Guide
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx
Part No. 24-11353-00028, Rev.
C
Issued May 2019
(barcode for factory use only)
24-11353-00028, Rev. C
*241135300028C*

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers

  • A
    adeanSep 16, 2025
    What does 'Changeover Fail' mean on my Johnson Controls Controller and how to fix it?
    • C
      Crystal WilliamsSep 16, 2025
      If your Johnson Controls Controller displays 'Changeover Fail', it indicates that the Supply Temperature Sensor is either not installed, has failed, or has been disconnected. As a result, the TEC can't detect the changeover mode for cooling or heating. You can follow the same troubleshooting steps as for a 'Supply Temp Fail' alarm.
  • R
    Robert ParkerSep 16, 2025
    How to resolve a 'Board Mismatch' error on my Johnson Controls Controller?
    • J
      James KirkSep 16, 2025
      If your Johnson Controls Controller displays 'Board Mismatch', it means the baseboard and CPU board are not correctly paired. The TEC will show an error message with the model numbers of both boards. To fix this, match the baseboard to its corresponding CPU board.
  • C
    Curtis BruceSep 16, 2025
    What causes 'Humidity Unreliable' on a Johnson Controls Controller?
    • H
      harold77Sep 16, 2025
      If the zone humidity reading on your Johnson Controls Controller was reliable but has now failed, and if the source of zone humidity was the onboard sensor, contact Johnson Controls product sales and support. If the source was a BAS, check the BAS to ensure it's online and providing the TEC with the humidity reading. If you intentionally removed the BAS mapping, reset the sensors through the menu.
  • M
    Michael SmithSep 16, 2025
    How do I fix a 'Firmware Mismatch' error on my Johnson Controls Controller?
    • K
      Kevin SpenceSep 16, 2025
      If your Johnson Controls Controller displays 'Firmware Mismatch', it means a previous upgrade or downgrade hasn't completed. If it's due to an incomplete upgrade, upgrade the TEC3000 to the latest released version, then upgrade it to the current version again. If it's an incomplete downgrade because the previous version is no longer supported, reboot the TEC3000 to clear the fault.
  • J
    John GrahamSep 16, 2025
    What to do if my Johnson Controls Controller shows 'Open Window'?
    • B
      brian56Sep 16, 2025
      If your Johnson Controls Controller displays 'Open Window' and control has shut down, it means the switch connected to the BI configured for Open Window is sensing that a window is open. To solve this: First, close the window. If the problem persists, check the sensor functionality with an ohmmeter and verify the wiring to the TEC. If needed, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • Y
    ywilkersonSep 16, 2025
    Why does my Johnson Controls Controller show 'Fan Lock'?
    • P
      perezrobinSep 16, 2025
      If your Johnson Controls Controller displays 'Fan Lock' and control has shut down, it means the switch connected to the BI configured for Fan Lock didn't sense airflow within 10 seconds of starting the fan. Here's how to address it: First, inspect the equipment to ensure the fan functions. Next, check the sensor functionality with an ohmmeter and verify the wiring to the TEC. Then, reset the fault by going to the menu, selecting Fault Status, and choosing Fan Lock. If the problem persists, you may need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • N
    Nancy MillerSep 16, 2025
    Why is 'Dehum Unavailable' on my Johnson Controls Controller?
    • J
      john27Sep 16, 2025
      If your Johnson Controls Controller displays 'Dehum Unavailable', it means dehumidification is unavailable because the zone humidity sensor has either failed or the humidity reading isn't reliable. If the zone humidity source was a BAS, check the BAS to ensure it's online and providing the TEC with the humidity reading. If you intentionally removed the BAS mapping, reset the sensors through the menu. If the problem continues, you may need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • D
    Deborah LynchSep 16, 2025
    What does 'USB Malfunction' mean on my Johnson Controls Controller?
    • H
      harpermichaelSep 16, 2025
      If your Johnson Controls Controller displays 'USB Malfunction', it means a USB drive has malfunctioned and drawn too much current. First, try inserting the USB drive again. If that doesn't work, try a different USB drive. If the problem persists, you might need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • J
    Jacob PierceSep 17, 2025
    Why does the zone temperature change too much in unoccupied mode on my Johnson Controls Controller?
    • A
      Andrea ShermanSep 17, 2025
      If the zone space temperature on your Johnson Controls Controller increases or decreases too much when the unit is active in unoccupied mode, it's likely that the heating and cooling equipment are too big for the unoccupied space. To fix this, decrease the Unoccupied Off Delay parameter from 10 minutes to a more suitable time for your equipment configuration.
  • D
    Denise AlexanderSep 17, 2025
    What does 'Supply Fan Runtime Limit Extended' mean on my Johnson Controls Controller?
    • J
      Jacob LoveSep 18, 2025
      If your Johnson Controls Controller displays 'Supply Fan Runtime Limit Extended', it means the supply fan runtime has exceeded the configured limit. You should service the supply fan and then reset the supply fan runtime.

Summary

Installation Procedures

Optimal Location Considerations

Guidelines for selecting the best placement for controller performance.

Mounting and Securing the Controller

Step-by-step guide for physically installing the thermostat controller.

Wiring Procedures and Safety

Electrical Safety and Precautions

Warnings about shock hazards, property damage, and ESD during wiring.

Terminal Connections and EOL Setup

Instructions for wiring terminals and setting the bus end-of-line switch.

Setup and Display Customization

User Interface and Operational Features

USB Port for Firmware and Backups

Guide for using the USB port for upgrades, backups, and restoring settings.

Controller Configuration and Modes

Scheduling and Occupancy Control

Troubleshooting Common Issues

Diagnosing and Resolving Faults

Lists common faults, their causes, and recommended solutions.

Symptom-Based Troubleshooting Guide

Detailed steps to diagnose and fix specific operational problems.