TEC3000 Series Networked and Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with Dehumidification Capability
Quick Start Guide
1
Refer to the QuickLIT website for the most up-to-date version of this document.
North American emissions compliance
United States
Canada
Installation
Parts included
One TEC3000 Series Thermostat Controller with integral mounting base
One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series Thermostat Controller:
On a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature, allowing
for vertical air circulation to the TEC
Away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, stairwells, and
from
b
ehind doors
Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
In a clear path between the integrated passive infrared (PIR) occupancy sensor (if equipped) and the spac
e
be
ing monitored
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
TEC3000 Series Networked and Wireless Proportional Fan
Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability
Quick Start Guide
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx, TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx
Part No. 24-11353-00028, Rev.
C
Issued May 2019
(barcode for factory use only)
24-11353-00028, Rev. C
*241135300028C*

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers

  • R
    randy35Sep 14, 2025
    What should I do if my Johnson Controls Controller shows 'Calibration Corrupt'?
    • R
      rachelgonzalesSep 14, 2025
      If the Johnson Controls Controller displays 'Calibration Corrupt', order replacement units and return the affected devices to Johnson Controls under the RMA program. This indicates that the factory calibration data is lost or not installed.
  • D
    Diana WardSep 14, 2025
    What to do if Johnson Controls Controller displays 'Zone Temp Unreliable'?
    • D
      dylanlindseySep 15, 2025
      If the Johnson Controls Controller displays 'Zone Temp Unreliable', order replacement units and return the affected devices to Johnson Controls under the RMA program. This indicates that all sources of zone temperature, including the onboard sensor, are unreliable.
  • C
    Christina GriffinSep 15, 2025
    How to fix 'The controller displays Controller Fault' on Johnson Controls Controller?
    • C
      Curtis McclainSep 15, 2025
      If your Johnson Controls Controller displays 'The controller displays Controller Fault', order replacement units and return the affected devices to Johnson Controls under the RMA program. This is because an internal fault was detected and the controller was unable to recover.
  • S
    Sarah CarneySep 15, 2025
    What does 'Controller Fault' mean on my Johnson Controls Controller?
    • T
      Thomas MooneySep 15, 2025
      Order replacement units and return the affected devices to Johnson Controls under the RMA program. This is due to an internal fault that the controller cannot recover from.
  • R
    Ruth WalkerSep 15, 2025
    What does 'Board Mismatch' mean on my Johnson Controls Controller?
    • D
      Deborah CooperSep 15, 2025
      Match the baseboard to its corresponding CPU board. The error message on the TEC indicates the model number of the baseboard and CPU board. This issue appears because the baseboard and CPU board are paired incorrectly.
  • R
    Richard BeardSep 15, 2025
    Why does my Johnson Controls Controller show 'Supervisory Status = Offline'?
    • S
      Steven CruzSep 15, 2025
      For wireless models, if the Supervisory Status is Offline, map the TEC into a JCI Supervisory system. Verify that the PAN’s WNC or WRG Gateway is online. Add ZFR182x or ZFR183x Routers/Repeaters into the wireless system. The supervisory controller is not communicating with the TEC, the TEC is not mapped to a JCI Supervisory System, or the WNC or WRG Gateway is not communicating with the TEC.
  • C
    curtis87Sep 15, 2025
    What to do if the touchscreen is unavailable on my Johnson Controls Controller?
    • A
      Alexander SwansonSep 15, 2025
      If the touchscreen components on your Johnson Controls Controller have failed to initialize, try rebooting the controller. If the problem continues, you may need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • A
    Annette RomeroSep 15, 2025
    How to fix a 'Remote Zone Temp Fail' error on a Johnson Controls Controller?
    • D
      David PetersonSep 15, 2025
      If your Johnson Controls Controller displays 'Remote Zone Temp Fail', it means the external zone temperature sensor is either disconnected or has failed. First, check the sensor wiring. If you intentionally disconnected it, reset the sensors through the menu. If the issue persists, you may need to order replacement units and return the faulty devices to Johnson Controls under the RMA program.
  • A
    Alan JohnsonSep 15, 2025
    How to troubleshoot a 'Supply Temp Fail' error on a Johnson Controls Controller?
    • T
      Tamara BassSep 15, 2025
      If your Johnson Controls Controller displays 'Supply Temp Fail', the external supply temperature sensor is either disconnected or has failed. You can try these steps: First, check the sensor wiring. If intentionally disconnected, reset the sensors by going to the menu, then Control Setup, and selecting Inputs. If the problem continues, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • S
    Samantha MarshallSep 15, 2025
    Why is the TEC3000 zone temperature not changing fast enough on my Johnson Controls Controller?
    • L
      Luis JohnsonSep 15, 2025
      If the TEC3000 zone temperature on your Johnson Controls Controller isn't changing fast enough compared to a calibrated sensor, it might be because the TEC3000 is set up for larger spaces by default when a proportional device is active. To resolve this, go to Control Setup > Tuning > Equipment Size and select 'Oversized'.

Summary

Installation Procedures

Optimal Location Considerations

Guidelines for selecting the best placement for controller performance.

Mounting and Securing the Controller

Step-by-step guide for physically installing the thermostat controller.

Wiring Procedures and Safety

Electrical Safety and Precautions

Warnings about shock hazards, property damage, and ESD during wiring.

Terminal Connections and EOL Setup

Instructions for wiring terminals and setting the bus end-of-line switch.

Setup and Display Customization

User Interface and Operational Features

USB Port for Firmware and Backups

Guide for using the USB port for upgrades, backups, and restoring settings.

Controller Configuration and Modes

Scheduling and Occupancy Control

Troubleshooting Common Issues

Diagnosing and Resolving Faults

Lists common faults, their causes, and recommended solutions.

Symptom-Based Troubleshooting Guide

Detailed steps to diagnose and fix specific operational problems.