EasyManua.ls Logo

Johnson Controls VB09 - Cleaning the System; FIGURE 20 - System Flushing and Cleaning

Johnson Controls VB09
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
1
10. Continue to bleed the system until the water leav-
ing the drain is clear, no less than 2 hours.
11. Completely drain the piping system.
Cleaning the System
1. After the initial ushing, chemically clean the
system. Repeat the method in Flushing the System
on page 28 to rell the system and circulate the
cleaning solution.
It is recommended to use the services of a pro-
fessional water treatment company for the type of
solution to be used and the duration of the clean-
ing application.
2. Once the cleaning process is complete, shut off
the circulating pump and completely drain the
system.
3. Rell the system with clean water to prepare for
refrigeration chassis connection and system start-
up.
It is recommended that a professional wa-
ter treatment company perform ongoing
maintenance of the water loop including
chemical analysis and ushing, if neces-
sary. The water loop testing should be per-
formed at intervals recommended by the
professional water treatment consultant.
It is recommended that the water loop
testing be performed at least once a year.
Standard practice is once a month or
quarterly.
The customer is responsible for complet-
ing adequate water loop maintenance
over the lifespan of the units. Otherwise,
damage to the units may occur.
Stub-outs
to chassis
Hose or piping
connecting
supply & return
runouts
Supply
Riser
Return
Riser
Hose or piping
connecting supply
and return runouts
Stub-outs to
chassis
Supply
Riser
Return
Riser
LD19685
FIGURE 20 - SYSTEM FLUSHING AND CLEANING

Table of Contents

Related product manuals