System screen
Figure 28: System screen
This screen gives a general overview of common chiller parameters for both shells.
Table 17: Display only fields
Field/LED name Description
Discharge Temperature Displays the temperature of the refrigerant in its gaseous state at discharge of the
compressor as it travels to the condenser.
Input % Full Load Amps This displays the percentage of full load amps used by the system.
Input Current Limit setpoint Displays the current limit value in use. This value is percent of Input Full Load Amps.
Condenser Liquid
Temperature - Leaving
Displays the temperature of the liquid as it leaves the condenser.
Condenser Liquid
Temperature - Entering
Displays the temperature of the liquid as it enters the condenser.
Chilled Liquid Temperature -
Leaving
Displays the temperature of the liquid as it leaves the evaporator.
Chilled Liquid Temperature -
Entering
Displays the temperature of the liquid as it enters the evaporator.
Chilled Liquid Temperature -
setpoint
Displays the programmed temperature setpoint for leaving chilled liquid. It is the local value
or remote reset value depending on control source.
Condenser Pressure Displays the refrigerant pressure in the condenser.
Condenser Saturation
Temperature
Displays the saturation temperature in the condenser calculated from condenser pressure.
Evaporator Pressure Displays the present refrigerant pressure in the evaporator.
Evaporator Saturation
Temperature
Displays the present saturation temperature in the evaporator calculated from evaporator
pressure.
39
YMC
2
Mod B with OptiView Control Center