Table 16: ZY04 to 12 High Static Indoor Blower - With Powered Convenience Outlet (with VFD)
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 49.6 50 60 53 262 51.8 60 60 56 272
11725 12 1 33.3 59.4 60 60 55 262 62.1 70 70 57 272
12525 18.6 1 51.6 82.3 90 90 76 262 85 90 90 78 272
13225 24 1 66.6 101 110 110 93 262 103.8 110 110 95 272
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.9 1.1 8.6
14225 31.8 2 88.3 128.1 150 150 118 262 130.9 150 150 120 272
None - - - 49.1 50 60 53 271 51.1 60 60 55 266
11725 16 1 38.5 65.3 70 70 60 271 67.8 70 70 62 266
12525 24.8 1 59.7 91.8 100 100 84 271 94.3 100 100 87 266
13225 32 1 77 113.4 125 125 104 271 115.9 125 125 107 266
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.4 1 8.6
14225 42.4 2 102 144.6 150 150 133 271 147.1 150 150 135 266
None - - - 23.5 25 25 25 136 24.5 25 25 26 132
11746 16.5 1 19.8 33.3 35 35 31 136 34.6 35 35 32 132
12846 27.8 1 33.4 50.3 60 60 46 136 51.6 60 60 47 132
13346 33 1 39.7 58.2 60 60 54 136 59.4 60 60 55 132
460-3-60 6.2 41 10 6.2 41 10 1.3 4.7 0.5 8.6
14246 41.7 2 50.2 71.3 80 80 66 136 72.6 80 80 67 132
None - - - 19 20 20 20 117 19.8 20 20 21 114
11758 17 1 16.4 28 30 30 26 117 29 30 30 27 114
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 4.3 0.4 8.6
13458 34 1 32.7 48.4 50 50 45 117 49.4 50 50 45 114
None - - - 59.6 60 70 64 349 61.8 70 70 66 359
11725 12 1 33.3 63.9 70 70 64 349 66.6 70 70 66 359
12525 18.6 1 51.6 86.8 90 90 80 349 89.5 90 90 82 359
13225 24 1 66.6 105.5 110 110 97 349 108.3 110 110 100 359
208-3-60 16 110 25 16 110 25 5.8 13.5 1.1 8.6
14225 31.8 2 88.3 132.6 150 150 122 349 135.4 150 150 125 359
None - - - 58.9 60 70 63 345 60.9 70 70 65 350
11725 16 1 38.5 70.3 80 80 65 345 72.8 80 80 67 350
12525 24.8 1 59.7 96.8 100 100 89 345 99.3 100 100 91 350
13225 32 1 77 118.4 125 125 109 345 120.9 125 125 111 350
230-3-60 16 110 25 16 110 25 5.2 13.4 1 8.6
14225 42.4 2 102 149.6 150 150 138 345 152.1 175 175 140 350
None - - - 29.4 30 35 32 168 30.4 35 35 33 170
11746 16.5 1 19.8 35.8 40 40 33 168 37.1 40 40 34 170
12846 27.8 1 33.4 52.8 60 60 49 168 54.1 60 60 50 170
13346 33 1 39.7 60.7 70 70 56 168 61.9 70 70 57 170
460-3-60 7.8 52 12 7.8 52 12 2.9 6.7 0.5 8.6
14246 41.7 2 50.2 73.8 80 80 68 168 75.1 80 80 69 170
None - - - 22.1 25 25 24 131 22.9 25 25 25 133
11758 17 1 16.4 29.4 30 30 27 131 30.4 35 35 28 133
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 5.4 0.4 8.6
13458 34 1 32.7 49.8 50 50 46 131 50.8 60 60 47 133
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A62