Connect the EX4400 to Power
IN THIS SECTION
Connect Earth Ground to an EX4400 Switch | 162
Connect AC Power to an EX4400 Switch | 163
Connect DC Power to an EX4400 Switch | 165
Connect Earth Ground to an EX4400 Switch
To ensure proper operaon and to meet safety and electromagnec interference (EMI) requirements,
you must connect the EX4400 switch to earth ground before you connect power to the switch. You
must use the protecve earthing terminal on the switch chassis to connect the switch to earth ground
(see Figure 99 on page 163).
You must install the EX4400 switch in a restricted-access locaon and ensure that the chassis is always
properly grounded. EX4400 switches have a 2-hole protecve grounding terminal on the rear panel of
the chassis. Under all circumstances, use this grounding connecon to ground the chassis. For AC-
powered systems, you must also use the grounding wire in the AC power cord along with the two-hole
grounding lug connecon. This tested system meets or exceeds all applicable EMC regulatory
requirements with the two-hole protecve grounding terminal.
CAUTION: Ensure that a licensed electrician has aached the appropriate grounding lug
to the grounding cable that you supply. Using a grounding cable with an incorrectly
aached lug can damage the switch.
To ground the EX4400 system, you can use either LCD10-10AF-L or LCD8-AF-L two hole lug. Use
14AWG ( 2mm2) wire or as per local code if you are using LCD10-AF-L or use 8 AWG (8mm2) wire or as
per local code if you are using LCD8-AF-L.
To ground the EX4400 switch:
1. Connect one end of the grounding cable to a proper earth ground, such as the rack in which the
switch is mounted.
2. Place the grounding lug aached to the grounding cable over the protecve earthing terminal on the
rear panel (see Figure 99 on page 163).
162