805.15
K-Commander Loss-in-Weight Programming
Rev: G Produced by the K-Tron Institute
LWF Page 01: Feed Factor Setup, Continued
Page 01
variable list
The following is a listing and description of each variable on this page.
A "` " mark shows the values that you can edit. A "#" indicates that the
value is changed by a Function key.
Variable Name Edit? Description
Initial Feedfactor `
This value of feedfactor is used for
two purposes:
1 ] To set Drive Command when in
Vol control by the formula.....
DC(%) = (SP/IFF )*100%
where SP = setpoint and DC =
Drive Command.
2 ] The Initial Feedfactor multiplied
by the Feedfactor Alarm Limit
value is how much the Average
Feedfactor can wander without a
feedfactor alarm.
ex: Initial Feedfactor (IFF) = 1000
Feedfactor alarm = 10%
Max Ave FF = 1100
Min Ave FF = 900
If the average Feedfactor goes
beyond the max or min limit, a
feedfactor alarm results.
Range of Values
0 to 100,000,000
Default value: 0.012
Continued on next page