805.14
K-Commander Loss-in-Weight Programming
Rev: G Produced by the K-Tron Institute
LWF Page 01: Feed Factor Setup
Introduction:
Page 01
The page 01 for the loss-in-weight feeder holds the information
regarding feed factors. There are various feeding factors used by the
controller. Please refer to the LWF Control section for additional
information. Use the Scroll keys to move from page to page.
Page 01 layout
This diagram shows the data layout. The second row of keys pop up when
the Edit key is pressed and a variable is highlighted.
Edit
Mode
F5 F6 F7 F8F1 F2 F3
F4
POWDER LWF : Feed Factors M01.01
INITIAL FEEDFACTOR 1878.000
AVERAGE FEEDFACTOR 1731.002
FF HOPPER EMPTY 1656.607
FF HOPPER MID 1698.667
FF HOPPER FULL 1735.998
DENSITY ARRAY On
FEEDFACTOR ALARM LIMIT 0.000 %
CALIBRATE DRIVE COMMAND 10 %
CALIBRATE TIME 60 sec
CALIB. CORRELATION LIMIT 84.2
LAST CALIB. CORRELATION 87.7
MATERIAL FED LAST CALIB. 2.8850
Grav
Mode
Vol
Mode
Calibrate
Cycle
F5 F6 F7 F8
Change
Value
<ESC>
Continued on next page