K-Commander Loss-in-Weight Programming
Rev: G Produced by the K-Tron Institute
LWF Page 02: Refill Parameters, Continued
Page 02
variable list
The following is a listing and description of each variable on this page.
A "` " mark shows the values that you can edit. A "#" indicates that the
value is changed by a Function key.
Variable Name Edit? Description
Refill Enable `
No Refill
Refill <
You select Refill to have the
Automatic function, if selected,
continue to activate the refilling
process. If you select "No Refill" ,
no refill will occur and this will
allow you to clean out the feeder
hopper with no problems. The
default value is " Refill".
Allowed Refill Time ` This entry sets the time period for a
normal refill-in Automatic Refill
mode- to occur. If the refill takes
longer than this entered value, an
alarm and an output from the Refill
Timer Output will occur.
Range of Values
5 to 240 seconds
Default value: 30 seconds
Continued on next page