Loading...
ASD 25 ASD 30 ASD 40S ASD 40
Maximum working pres‐
sure [psig]
(heat transfer medium)
145 145 145 145
Max. permissible dis‐
charge temp. [ °F]
212 212 212 212
Pressure drop [psi] <1.5 <1.5 <1.5 <1.5
Unsuitable heat transfer
media
Seawater
Consult KAESER before using another type of heat transfer medium.
Tab. 23 Heat exchanger specification (option W2/W3)
Heat capacity
Maximum heat capacity
available
ASD 25 ASD 30 ASD 40S ASD 40
[kW] 16.4 19.3 23.9 27.6
[MJ/h] 59 69 86 99
[kcal/h] 14101 16578 20567 23732
Tab. 24 Heat capacity (option W2/W3)
Flow rate for heating from 110 °F to 160 °F (ΔT=25K)
ASD 25 ASD 30 ASD 40S ASD 40
Flow rate [gpm] 2.51 2.95 3.70 4.62
Tab. 25 Flow rate (option W2)
Flow rate for heating from 60 °F to 160 °F (ΔT=55K)
ASD 25 ASD 30 ASD 40S ASD 40
Flow rate [gpm] 1.10 1.32 1.63 1.89
Tab. 26 Flow rate (option W3)
2.16 Refrigeration dryer
Model
ASD 25 ASD 30 ASD 40S ASD 40
Model*
*Transfer data from dryer
nameplate to the table.
Tab. 27 Refrigeration dryer: model