Fig. 1 Maximum relative humidity
T Inlet air temperature [°F]
H Maximum relative humidity of inlet air [%]
2.6 Ventilation
The values given are minimum guide values.
BSD 40 BSD 50 BSD 60
Inlet aperture Z see fig‐
ure 11 [sq.ft.]
8.6/2.2* 10.8/2.2* 12.9/2.2*
Forced ventilation with ex‐
haust fan:
Flow rate [cfm] at 0.4 in wc
6474
942*
7946
1177*
9712
1471*
Exhaust duct:
Dimensions [in]
27 1/2 x 27 1/2 27 1/2 x 27 1/2 27 1/2 x 27 1/2
* Option K2
Tab. 7 Ventilation
2.7 Pressure
Maximum working pressure: see nameplate
Safety relief valve blow-off setting [psig]:
Maximum working pres‐
sure [psig]
BSD 40 BSD 50 BSD 60
125 155 155 155
175 230 230 230
217 232 232
Tab. 8 Safety relief valve setting