Commissioning of the machine may only be carried out by trained and authorized installation or
maintenance personnel.
Special measures for re-commissioning after storage
Storage period
longer than...
Remedy
12 months Change the oil filter.
Change the oil separator cartridge.
Change the cooling oil.
Have the motor bearings checked by an authorized KAESER Service repre‐
sentative.
36 months Have the overall technical condition checked by an authorized KAESER Ser‐
vice representative.
Tab. 40 Re-commissioning after storage
7.3 Checking installation and operating conditions
Check and confirm all the items in the checklist before initially starting the machine.
To be checked See
chapter
Confirmed?
Are the operators fully familiar with safety regulations?
Have all the positioning conditions been fulfilled? 5
Is a user's lockable power supply disconnecting device installed? 6.4
Does the power supply conform to the specifications on the name‐
plate?
2.1
Are the power supply cable conductor cross-sections and fuse ratings
adequate?
2.14
Drive motor overload protection switch set according to the main power
supply voltage?
7.4
Fan motor overload protection switch set according to the main power
supply voltage?
7.5
Have all electrical connections been checked for tightness?
(The check must be repeated after 50 operating hours)
Is a shut-off valve fitted to compressed air outlet? 6.3
Has the connection to the air system been made with a hose or axial
compensator?
6.3
Sufficient cooling oil in the separator tank?
(oil level indicator outside the red zone)
10.13
Is there sufficient cooling oil in the airend? 7.6
Is the machine firmly anchored to the floor?
(option H1)
6.5.1
Supply of cooling water ensured?
(option K2)
6.5.2
7 Initial Start-up
7.3 Checking installation and operating conditions
9_5708 08 USE
Service Manual Screw Compressor
BSD
43

Table of Contents