Additionaly, the tariff provides the works with valuable
statistical data, when calculating new plant activities.
E=2) Flow-controlled tarif
When the actual water flow (Q) - in l/h or m³/h - is
larger than TL2, but smaller than TL3, thermal energy
is counted in TA2, parallel to the main register. If the
actual water flow exceeds TL3, thermal energy will
instead be counted in TA3, parallel to the main register.
Q < TL2 Counting in main register only
TL3 > Q > TL2 Counting in TA2, plus main register
Q > TL3 Counting in TA3, plus main register
When programming data, be sure to enter a value for
TL3 that is larger than TL2.
As with the power-controlled tariff, the flow-controlled
tariff can be used as a basis for calculating the
individual consumer’s connection fee.
Additionaly, the tariff provides the works with valuable
statistical data, when calculating new plant activities.
E=3) Cooling tariff (
DD
DD
Dt)
When the actual cooling (Dt), in °C, is lower than TL2,
but larger than TL3, thermal energy is counted in TA2
parallel to the main register. If the actual cooling falls
below the TL3, thermal energy is counted in TA3
parallel to the main register.
Dt > TL2 Counting in main register only
TL3 < Dt < TL2 Counting in TA2, plus main register
Dt < TL3 Counting in TA3, plus main register
When programming data, be sure to enter a value for
TL3 that is smaller than the value for TL2.