Operating Instructions | KBL 4800 alpha
48
10.14 Ventilation and
air-conditioning
↵
In order to preserve the performance of the air-
conditioning unit, clean the heat exchangers after
500 - 600 hours of operation.
㉗
㉙
㉘
Airconditioning
unit
㉗ Heat exchanger
㉘ Condensate pump
㉙ Condensate tray
⇒
Open the bed part.
㉗
Clean the heat exchanger.
Vacuum it carefully, paying attention not to
damage the fins.
SERVICING THE VENTILATION SYSTEM
⇒
Check all hose connections.
⇒
Remove any kinks in the air hoses. Replace
defective hoses immediately.
The exhaust air hose must not exceed a
maximum length of 6 m if there is no auxiliary
fan installed.
CHECKING THE CONDENSATE PUMP
The condensate pump ㉘ pumps away the
condensation water at timer-controlled intervals.
Check the function of this pump with each tube
replacement.
⇒
Fill some water into the condensate tray ㉙.
Use a hose and a funnel to do so.
Make sure that the water does not spill over.
⇒
Start a tanning session and then wait for 20
minutes.
⇒
The filling level of the tray must then be below
the pump level.