Description of the display window
Sampling rate:
The power frequency tracing settings are displayed in this submenu. The setting "Auto"
causes the sampling rate to be traced automatically, within a range of 40 to 70 Hertz.
Alternatively, a xed sampling rate of 50 Hz or 60 Hz can be set.
Stage power monitored:
Monitoring of the stage power can be activated or deactivated in this submenu. Only
stages the stage power of which has been recorded in the learning mode are moni-
tored.
The manually congured stage power is not taken into account, as it is assumed that
the stage power has been congured in accordance with the nameplate of the compen-
sation stage.
Functional principle:
Each time a capacitor stage is switched on, a check is performed to determine whether
a change of current takes place in the main current transformer. If this is not the case,
the stage is marked with an X in the start menu window. This may be for one of the
following reasons and needs to be checked:
• Capacitor faulty
• Contactor faulty
• Fuse faulty
Reset:
The Reset menu item oers various methods of resetting the programmed controller
parameters. The programmable parameters are reset to the default settings.
This has the advantage that all congured parameters are deleted at the same time and
the controller restarts with the default settings.
Perform reset:
Extras menu, Reset menu item
Press U = Reset ashes
Press U and V simultaneously = done is displayed
After about 2 seconds, Reset is displayed again
NOTE
The reset process can be interrupted by pressing X.
Contrast setting:
The contrast settings of the LCD can be changed in this submenu.
Setting range: 0 to 10.