Address Words Description Value Format
Stage parameters
0xD080 2 Base index for the following stage
parameters
(addresses 0xD080 to 0xD08E)
0 (= stage 1) unsigned
long
0xD082 2 Mode 0 = O // 1 =
Auto 2 = On
unsigned
long
0xD084 2 Stage power [0.1 kvar] 0-9999 unsigned
long
0xD086 2 Discharge time [s] 0-999 unsigned
long
0xD088 2 Operating cycles 0-999999 unsigned
long
0xD08A 2 0 unsigned
long
0xD08C 2 0 unsigned
long
0xD08E 2 0 unsigned
long
0xD090 2 Base index for the following stage pa-
rameters (addresses 0xD090 to 0xD09E)
1 (= stage 2) unsigned
long
0xD09E 2 0 unsigned
long
0xD0A0 2 Base index for the following stage
parameters
(addresses 0xD0A0 to 0xD0AE)
2 (= stage 3) unsigned
long
0xD0AE 2 0 unsigned
long
0xD0B0 2 Base index for the following stage
parameters
(addresses 0xD0B0 to 0xD0BE)
3 (= stage 4) unsigned
long
0xD0BE 2 0 unsigned
long
Data point description for the Modbus protocol