 Full Name Type 
A01
A01
Sucon Pres Sensor [Group 1]
Alarm
Alarm - Crical
Group 1 sucon pressure sensor is shorted, open or pressure
out of range.
A02
A02
Disch Pres Sensor [Group 1] Alarm Alarm - Crical
Group 1 discharge pressure sensor is shorted, open or pres-
sure out of range.
A03
A03
Sucon Temp Sensor [Group 1]
Alarm
Alarm - Crical Group 1 sucon temperature sensor is shorted or open.
A04
A04
Disch Temp Sensor [Group 1] Alarm - Crical Group 1 discharge temperature sensor is shorted or open.
A06
A06
High Superheat [Group 1] Alarm Alarm - Cauonary
Group 1 sucon superheat is higher than Max Sucon SH
for longer than Min/Max SH Del.
A07
A07
Low Superheat [Group 1] Alarm Alarm - Crical
Group 1 sucon superheat is lower than Min Sucon SH for
longer than Min/Max SH Del.
A08
A08
High Disch Temp [Group 1] Alarm Alarm - Crical
Group 1 discharge temperature is higher than Max Disch
Temp for longer than Max Dis Tmp Del.
A09
A09
High Int Comp Temp [Group 1]
Alarm
Alarm - Cauonary
Group 1 digital compressor internal temp high. Will turn o
digital compressor unl temp lowers.
A10
A10
High Disch Pres [Group 1] Alarm Alarm - Crical
Group 1 discharge pressure is higher than Max Disch Pres
for longer than Max Dis Prs Del.
A13
A13
Comp Mod [Group 1] Alarm Alarm - Cauonary Group 1 Compressor Module digital input is acve.
A16
A16
Oil Safety [Group 1] Alarm Alarm - Cauonary Group 1 Oil Safety digital input is acve.
A19
A19
Hi Pres Safety [Group 1] Alarm Alarm - Cauonary Group 1 High Pressure Safety digital input is acve.
A22
A22
Aux Brd Comms Alarm Alarm - Crical Main Board unable to communicate w. the Aux Relay Boards.
A25
A25
Watchdog Alarm Alarm - Cauonary Contact KE2 Therm.
A26
A26
Email Failure Alarm Alarm - Cauonary
Email alert was not conrmed by email server provided aer
seven consecuve aempts.
A28
A28
High Disch Temp [Group 2] Alarm Alarm - Crical
Group 2 discharge temperature is higher than Max Disch
Temp for longer than Max Dis Tmp Del.
A29
A29
Evap Comms [Group 1] Alarm Alarm - Cauonary Group 1 Siteview controllers not communicang.
A30
A30
Evap Comms [Group 2] Alarm Alarm - Cauonary Group 2 Siteview controllers not communicang.
A31
A31
Disch Pres Sensor [Group 2] Alarm Alarm - Crical
Group 2 discharge pressure sensor is shorted, open or pres-
sure out of range.
A32
A32
Sucon Temp Sensor [Group 2]
Alarm
Alarm - Crical Group 2 sucon temperature sensor is shorted or open.
A34
A34
High Superheat [Group 2] Alarm Alarm - Cauonary
Group 2 sucon superheat is higher than Max Sucon SH
for longer than Min/Max SH Del.
A35
A35
Low Superheat [Group 2] Alarm Alarm - Crical
Group 2 sucon superheat is lower than Min Sucon SH for
longer than Min/Max SH Del.
A36
A36
Disch Temp Sensor [Group 2] Alarm Alarm - Crical Group 2 discharge temperature sensor is shorted or open.
A37
A37
High Int Comp Temp [Group 2]
Alarm
Alarm - Cauonary
Group 2 digital compressor internal temp high. Will turn o
digital compressor unl temp lowers.
A38
A38
High Disch Pres [Group 2] Alarm Alarm - Crical
Group 2 discharge pressure is higher than Max Disch Pres
for longer than Max Dis Prs Del.
A41
A41
Sucon Pres Sensor [Group 2]
Alarm
Alarm - Crical
Group 2 sucon pressure sensor is shorted, open or pressure
out of range.
A44
A44
Comp Mod [Group 2] Alarm Alarm - Cauonary Group 2 Compressor Module digital input is acve.
A47
A47
Oil Safety [Group 2] Alarm Alarm - Cauonary Group 2 Oil Safety digital input is acve.
A50
A50
Hi Pres Safety [Group 2] Alarm Alarm - Cauonary Group 2 High Pressure Safety digital input is acve.
A53
A53
Main: Aux Input 1 Sensor [Group
1] Alarm
Alarm - Cauonary Main Board, Aux Input 1 Sensor is shorted or open.
A54
A54
Main: Aux Input 2 Sensor [Group
1] Alarm
Alarm - Cauonary Main Board, Aux Input 2 Sensor is shorted or open.
A55
A55
Main: Aux Input 3 Sensor [Group
1] Alarm
Alarm - Cauonary Main Board, Aux Input 3 Sensor is shorted or open.
A56
A56
Aux Addr 1: Input 2 Sensor [Group
1] or [Group 2] Alarm
Alarm - Cauonary Aux Board 1, Input 2 Sensor is shorted or open.