GB - 14
Description of the Terminals
KEB generally recommends the use of wire-end ferrules in industrial environ-
ments.
4.2 Inputs
4.2.1 SpecicationoftheSTOinputs
STO
Inputs
Status 0 Status 1
UL [V] IL [mA] UH [V] IH [mA]
max. 5 15 30 15
min. -3 notdened 15 5