Further technical instructions KeContact P20
44 Installation manual, Version: 1.41 / Article no.: 90064
© KEBA 2012-2013
5.5 Technical data
Electrical data
Cable feed: Surface cable routing or flush-type cable routing
Mains connection cross-section: Minimum cross-section
(depending on the cable and the line length):
- 5 x 2.5 mm² (16A nominal current)
- 5 x 6.0 mm² (32A nominal current)
Mains supply terminals: Connection line:
- inflexible (min.-max): 0.2 – 16 mm²
- flexible (min.-max): 0.2 – 16 mm²
- AWG (min.-max): 24 – 6
- flexible (min.-max) with wire end sleeve
without/with plastic sleeve:
0.25 – 10 / 0.25 – 10 mm²
Mains supply terminals temperature rating:
105°C
Nominal current
(configurable connection values):
10A, 13A, 16A, 20A, 25A or 32A
3-phase or 1-phase
Mains voltage (Europe): 230V
230/400V 3N~
Line frequency: 50Hz / 60Hz
Overvoltage category: III according to EN 60664
Rated short-time withstand current: < 10kA effective value according to EN 61439-1
Fuse protection (in the house installation): The fuse protection must occur according to the
locally valid regulations, dependent on the socket
versions / cable versions (see type plate).
Residual current circuit breaker
(in the house installation):
RCD I
∆N
=30mA Type A, sensitive to pulse current
Dimension I
N
according to the fuse protection
Socket versions: Type 2 standard socket: 32A / 400 V
AC
according to EN 62196-1 and VDE-AR-E 2623-2-2
Cable versions:
(rating see type plate)
Type 1 cable: up to 32A / 230 V
AC
according to EN 62196-1 and SAE-J1772
Type 2 cable: up to 32A / 400 V
AC
according to EN 62196-1 and VDE-AR-E 2623-2-2
Equipment class: I
IP protection rating for device: IP54