Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
3.4.13 Latching faults (Yes/No - Address 000-127)
Setup menu > Alarm actions
When this function is set to Yes it requires a reset from the front panel or a remote
reset to clear fault indications. This is the factory default setting. It may be applied to
the Command Module or a Standard Detector.
3.4.14 Remote day/night (Yes/No - Address 001-127)
Setup menu > Alarm actions
Setting this function to Yes allows the detector to be manually switched between day
and night mode using a remote input.
3.4.15 Remote reset enable (Yes/No - Address 000-127)
Setup menu > Alarm actions
If remote resetting of the detector or Command Module is required from the host Fire
Alarm controller or other external source, this option must be set to Yes.
3.4.16 Remote Isolate Enable (Yes/No - Address 000-127)
Setup menu > Alarm actions
When this function is set to Yes a remote switch may be used to isolate the detector
or Command Module.
3.4.17 Programmed Isolate (Yes/No - Address 000-127)
Setup menu > Alarm actions
When set to Yes the controller will not generate alarms and will not indicate a
fault condition on any fire panel which is connected, e.g. for use during detector
maintenance. The ‘Fault’ light will be illuminated on the detector or Command Module
front panel. The isolated condition will be disabled automatically after 7 days if not
manually disabled.
3.4.18 Detector address / Number of detectors
(Display - Address 000-127)
Setup menu > Detector
In the case of the Standard Detector, this function displays the current address of
the detector as set by the internal DIP switch. On the Command Module, it shows
the number of detectors found on the communications loop. This function appears
immediately on entering the Detector submenu. The Command Module is always
at address ‘000’. When the Command Module unit is fitted in a detector, the
detector must have a separate address.