Page 4
Stratos  HSSD-2  •  INSTALLER’S  HANDBOOK  •  Iss.  12
The  Standard  Detector  may  be  operated  as  a  stand-alone  unit,  or  may  be  part  of  a 
network of detectors centrally monitored by a Command Module (see section 1.2).
It may be programmed via the front panel as in the version shown above. Alternatively, 
and  for  detectors  ordered  without  front  panel  display,  the  detector  may  be  pro-
grammed remotely via the detector’s RS485 terminals using a Command Module, or 
via the detector’s RS232 port using a PC running Remote Control software. A copy of
this software is packed with each detector supplied.
1.1 Standard Detector
1.2 Stand alone 
Command Module/ 
Command Module 
detector
1. Types of 
Detector
When multiple detectors are networked together, a Command Module may be used 
to tie  all  the  detectors together  and  to provide  a central point for  programming, 
running diagnostics and PC and fire panel connection.
The  Command  Module  can  be  mounted  either  inside  a  detector  as  shown  or  as  a 
stand-alone unit in its own housing without an aspirator or smoke detection circuitry. 
If  detectors  attached  to  the  Command  Module  are  mounted  in  different  fire  zones 
then the Command Module must be mounted in its own housing with separate power 
supply to comply with BS5839 and EN54.
When a Command Module is mounted inside a detector, the Standard Detector display 
is replaced with a dedicated Command Module display. The programming buttons and 
display on the front of the detector belong to the Command Module.
Programming from the Command Module is very similar to programming a detector, 
the main difference being that the Command Module has extra functions to control all 
the Stratos detectors connected to the detector loop.