Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
3.5 Menu map
Time HH:MM 
Date DD/MM/YYYY
Detector address
Device text
Aux
Pre Alarm+Fault
Fire 1+Fault 
Fire 2+Fault 
Fault
Delay override Enter Yes/No
Cascading alarms Enter Yes/No
Latching alarms Enter Yes/No
Latching faults Enter Yes/No
Remote day/night Enter Yes/No
Remote reset Enter Yes/No
Remote isolate Enter Yes/No
Prog. Isolate on Enter Yes/No
Fire 2 level (1-25) 
Fire 1 level (8-10)
Pre Alarm level (3-8)
Aux level (2-10)
Fire 2 delay (0-99)
Fire 1 delay (0-60)
Pre Alarm delay (0-60)
Aux delay (0-60)
Class. override (0-99)
Alarm factor (0-5)
Day start (0-23)
Night start (0-23)
LDD(TM) enable Enter Yes/No
FastLearn start Enter Yes/No
Auto FastLearn Enter Yes/No
Reference enable Enter Yes/No
Reference device (1-127)
Level (0-99)
Back off (0-99)
ISOLATE enable Enter Yes/No
TEST enable Enter Yes/No
RESET enable Enter Yes/No
Power save Enter Yes/No
Battery check Enter Yes/No
Mains check Enter Yes/No
Aspirator speed (1-16)
Flow setup Enter Yes/No
Sensor 'N' enable Enter Yes/No
Flow pipe 'N'
Flow low pipe 'N' (0-99)
Flow high pipe 'N' (0-99)
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.4.6
3.4.7
3.4.8
3.4.9
3.4.10
3.4.11
3.4.12
3.4.13
3.4.14
3.4.15
3.4.16
3.4.17
3.4.18
3.4.19
3.4.20
3.4.21
3.4.22
3.4.23
3.4.24
3.4.28
3.4.29
3.4.30
3.4.48
3.2
3.2
3.2
3.4.49
3.4.25
3.4.26
3.4.27
Alarm actions
Alarm levels
Time and Date
Detector
Reference
Front panel
Power checks
Air flow
Watchdog count
Relay test
Reset
Isolate
Exit
Setup Menu
Diagnostic menu
Log menu
Miscellaneous
Bus setup (CM only)
Menu
MAIN MENU
Submenu Item Para
Chart rate (0-5)
Access code (0-9999)
BMS protocol (0-2) (CM only)
Factory default Enter Y/N
Scan for devices Enter Yes/No
Numbers of detectors
Looped bus Enter Yes/No
Poll time out (30-255)
3.4.31
3.4.32
3.4.33
3.4.34
3.4.36
3.4.37
3.4.35
Pager (CM only)
Call centre
Password
Pager
Page on fault Enter Yes/No
Page on alarm Enter Yes/No
3.4.38
3.4.39
3.4.40
3.4.41
3.4.42
View event log
Diagnostics
Detector read
Loop errors
Dust separators
3.4.43
3.4.44
3.4.45
3.4.46
3.4.47
This sequence is repeated for each 
pipe 1-4 so that 'Flow high pipe 1' is
followed by 'Sensor 2 enable' etc.