Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
3. Programming
the unit
3.1 Engineering
Access code
The Stratos-HSSD-2 programmer means that programming and configuration of the
unit can be performed without opening the detector case.
To enter programming mode, press any of the program menu keys
,
or .
This correctly sets the access code. If an incorrect access code is entered or <RESET>
is pressed, the display will show Bad access code. Pressing a menu key will prompt
the user again for the correct access code.
Access code:0000
The Engineering Access code is required to allow the detector parameters to be
programmed. The access code is only valid whilst the user is in programming mode. It
will need to be entered again if programming mode is exited, if the detector is powered
down or if <RESET> is pressed.
To enter programming mode, press a menu key
, , . The unit responds by
displaying the prompt Access code:0000 asking for the engineering access code.
The factory default access code is 0102. To enter the default access code, follow the
sequence shown.
Note: Pressing
has no effect until is pressed to place the cursor under the
first digit.
Access code:0000 Access code:0000
Access code:0100
Access code:0102
Access code:0100 Access code:0100
Access code:0101
All of the programmable functions work in a similar manner. The
keys move the
cursor position through the user-settable digits and the
keys step through
the available values for the currently selected digit (e.g. 1 - 99, Yes / No etc) pressing
enters the displayed figure. Note that it is not possible to save an illegal value, e.g.
for the Fire 1 level the maximum valid input is 10 and it would be possible to enter 99,
but the programmer will display Bad value to inform you that the entry is invalid and
prompt for the value to be re-entered. All programmable parameters have the valid
input values range in brackets below the parameter legend on the display.
Having edited the value as required, press,
to select the amended setting.
Pressing when the cursor is on the right most digit has the same effect. If no
programming activity is detected for 5 minutes, the detector will display the legend
Access timeout and exit programming mode.