Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
14. Stratos-HSSD-2
specification
SELV rating (EN 60950) Class III
Supply Voltage 21.6V - 26.4V DC
PSU Type: conforming to EN 54-4
Electrical safety complies with IEC
61010-1
Size (mm) 427W x 372H x 95D
Weight 5.2kg (Detector) 5.3kg (Command
Module Detector) 6.2kg (Stand-alone
Command Module) 10.1kg (Stand-alone
Command Module + batteries)
Operating temperature range 0 to +38°C (UL 268 compliance)
-10 to + 60°C (EN 54-20 compliance)
Operating humidity range 0 - 90% Non Condensing
IEC 61010-1 Pollution degree 1
IEC 61010-1 Installation Cat. II
Sensitivity range (%Obs/m) Min = 25% Max = 0.03% FSD
Maximum sensitivity resolution 0.0015 %Obs/m
Detection principle Laser light scattering mass detection
Particle sensitivity range 0.0003µm to 10µm
Current consumption Detector: 300mA (fan speed 1), 470mA
(fan speed 8), 750mA (fan speed 16)
Command Module Detector: 750mA
(fan speed 1), 920mA (fan speed 8), 1.5A
(fan speed 16).
Stand-alone Command Module: 450mA
Relay contact rating 500mA @ 30V
Maximum sampling pipe length 200 metres total
Sampling pipe inlets 4
Sampling pipe internal diameter 15-25mm
Alarm levels 4 (Fire 2, Fire 1, PreAlarm and Aux)
Bargraph sensitivity range 0.0015 - 25% obs/m
Bargraph segments 26
Chamber service intervals Greater than 8 years (depending on
environment)
Dust separator replacement intervals Greater than 5 years (depending on
environment)
Laser lifetime (MTTF) Greater than 1000 years
Programming Front panel or PC via RS232/RS485
Data bus cable RS485 data cable
Data bus length 1.2 km IN, 1.2km OUT
IP rating IP50
Supported languages on Czech Dutch
internal programmer English Estonian
Finnish French
German Hungarian
Italian Norwegian
Spanish Swedish
This equipment is