Page 8
Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
2. Controls and
Indicators
Command Module
detector
Standard Detector
2 1 3
4
5 86
7
9
10
2
1
3
4
5 86
7
9
10
Aux, Pre-Alarm, Fire 1 and Fire 2 indicators illuminate when the appropriate
alarm level has been reached and the appropriate time delays have expired.
On a stand-alone Command Module, the indicators signify an alarm
condition from any detector on the communications loop.
Smoke density indicators. This display is in two sections. The first part,
labelled 1 to 10, is the relatively scaled ClassiFire
®
bargraph and changes in
steps of half a segment. The second part displays absolutely scaled smoke
levels above 1% obscuration per metre (% obs/m) to a maximum of 25%
obs/m. The Fire 2 activation level is programmed normally somewhere in
this range. The bargraph display will show a continually cycling pattern
when the unit is in FastLearn mode. On the Command Module display, this
will occur when any unit on the RS485 communications loop is in FastLearn.
Otherwise, the bargaph display on the Command Module will mimic the
bargraph display on the highest-reading detector on the loop.
Status display (if fitted). This display shows all events as they happen in real
time and is also used to configure the unit. See Section 3, ‘Programming
the unit‘ for more information.
RESET. When enabled, pressing <RESET> will clear any latched alarms
or faults and set the status display back to its normal operation display.
To comply with national standards, detectors are supplied with the RESET
function disabled as default.
1
2
4
5
3