Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
Because of the flexible nature of the Stratos-HSSD-2
®
detector and the many possible
configurations, there are many options for interfacing the detectors to the Fire Panel.
These include many third party interfaces available from various manufacturers. Because
of this, it is not possible to give a complete list of all interfacing methods but the
following pages will give details of the most common methods that are likely to be
used.
8.1 Setting the detector address
In order to identify itself to the Command Module or fire panel, each detector needs
to have a unique address ranging from 1 to 127. The detector address is simply set on
the red DIP switch SW1 at the bottom left of the opened detector on the main circuit
board. The switch settings are up for 1 and down for 0, and the detector address is set
as a 7-bit binary code (switch 8 equates to a value of 128 and so is outside the usable
address range). An example is shown below.
The address equates to 01100011 in binary, or (1 x 1) + (1 x 2) + (0 x 4) + (0 x 8) + (0
x 16) + (1 x 32) + (1 x 64) + (0 x 128) = 99
The full range of available addresses and their relevant switch settings are in section
8.1.1 for reference.
8. Interfacing
1
DIL ON
2 3 4 5 6 7 8